Wattage | 200W~3000W |
---|---|
Features |
TS Features
TN Features
IRC Features
|
Model No. Data Link | TS-200 / TS-400 / TS-700 / TS-1000 / TS-1500 / TS-3000 TN-1500 / TN-3000 IRC1 / IRC2 / IRC3 |
For more information or to speak with a Power 277 professional please call toll free: (877) 878-2348 or for international calls (001) 702-987-3111.
You can download and/or view the PDF specifications for TS-200 / TS-400 / TS-700 / TS-1000 / TS-1500 / TS-3000 TN-1500 / TN-3000 IRC1 / IRC2 / IRC3 above.
TS-700 Series
700W True Sine Wave DC-AC Power Inverter Features:
- True sine wave output (THD<3%)
- High surge power up to 1400W
- Standby saving mode can be selectable
- Front panel indicator for operation status
- Built-in fan ON-OFF control function
- Protections: Bat. low alarm / Bat. low shutdown / Over voltage / Over temp. / Output short / Reverse polarity / Overload
- Application : Home appliance, power tools, office and portable
- High efficiency up to 91%
- Power ON-OFF switch
- Equipment, vehicle and yacht …etc.
- 3 years warranty
MODEL | TS-700-112 | TS-700-124 | TS-700-148 | TS-700-212 | TS-700-224 | TS-700-248 | |
OUTPUT | RATED POWER (Typ.) | 700W | |||||
MAXIMUM OUTPUT POWER (Typ.) | 800W for 180 sec. / 1050W for 10 sec. / surge power 1400W for 30 cycles | ||||||
AC VOLTAGE | Factory setting set at 110VAC | Factory setting set at 230VAC | |||||
100 / 110 / 115 / 120VAC selectable by setting button S.W | 200 / 220 / 230 / 240VAC selectable by setting button S.W | ||||||
FREQUENCY | 60±0.1Hz 50/60Hz selectable by setting button S.W | 50±0.1Hz 50/60Hz selectable by setting button S.W | |||||
WAVEFORM Note.6 | True sine wave (THD<3%) | ||||||
AC REGULATION (Typ.) | ±3.0% | ||||||
SAVING MODE (Typ.) | Default disabled. Load?5W will be changed to standby mode | ||||||
FRONT PANEL INDICATOR | Battery voltage level, output load level, saving mode, fault and operation status | ||||||
INPUT | BAT. VOLTAGE | 12V | 24V | 48V | 12V | 24V | 48V |
VOLTAGE RANGE (Typ.)Note.3,5 | 10.5 ~ 15VDC | 21 ~ 30VDC | 42 ~ 60VDC | 10.5 ~ 15VDC | 21 ~ 30VDC | 42 ~ 60VDC | |
DC CURRENT (Typ.) | 75A | 38A | 19A | 75A | 38A | 19A | |
NO LOAD DISSIPATION (Typ.) | ?6W @ standby saving mode | ||||||
OFF MODE CURRENT DRAW | ?1mA | ||||||
EFFICIENCY (Typ.) Note.1 | 86% | 88% | 89% | 89% | 90% | 91% | |
BATTERY TYPES | Open & sealed Lead Acid | ||||||
BATTERY INPUT PROTECTION | FUSE | 40A*3 | 30A*2 | 20A*2 | 40A*3 | 30A*2 | 20A*2 |
BAT. LOW ALARM | 11.3±4% | 22.5±4% | 45±4% | 11.3±4% | 22.5±4% | 45±4% | |
BAT. LOW SHUTDOWN | 10.5±4% | 21±4% | 42±4% | 10.5±4% | 21±4% | 42±4% | |
BAT. POLARITY | By internal fuse open | ||||||
OUTPUT PROTECTION | OVER TEMPERATURE | 80?± 5? | 75?± 5? | ||||
Protection type : Shut down o/p voltage, re-power on to recover; by internal RTH3 detect on heatsink of power diode | |||||||
OUTPUT SHORT | Protection type : Shut down o/p voltage, re-power on to recover | ||||||
OVER LOAD (Typ.) | 105 ~ 115% load for 180 sec., 115% ~ 150% load for 10 sec. | ||||||
Protection type : Shut down o/p voltage, re-power on to recover | |||||||
GFCI PROCTECTION | Optional (Only type F) | None | |||||
ENVIRONMENT | WORKING TEMP. Note.4 | 0 ~ +40? @ 100% load ; +60? @ 50% load | |||||
WORKING HUMIDITY | 20% ~ 90% RH non-condensing | ||||||
STORAGE TEMP., HUMIDITY | -30 ~ +70? / -22 ~ +158oF, 10 ~ 95% RH | ||||||
VIBRATION | 10 ~ 500Hz, 3G 10min./1cycle, 60min. each along X, Y, Z axes | ||||||
SAFETY & EMC | SAFETY STANDARDS | Design refer to UL458 | None | ||||
LVD | None | EN60950-1 | |||||
WITHSTAND VOLTAGE | Bat I/P – AC O/P:3.0KVAC AC O/P – FG:1.5KVAC | ||||||
ISOLATION RESISTANCE | AC O/P-FG , Bat I/P-FG:100M Ohms / 500VDC / 25?/ 70% RH | ||||||
EMC EMISSION | Compliance to FCC class A | Compliance to EN55022 class A, 72/ 245/ CEE, 95/ 54/ CE, E-Mark | |||||
EMC IMMUNITY | None | Compliance to EN61000-4-2,3,8 | |||||
OTHERS | MTBF | 74.4K hrs min. MIL-HDBK-217F (25?) | |||||
DIMENSION | 295*184*70mm (L*W*H) | ||||||
PACKING | 3.8Kg; 2pcs/8.6Kg/1.27CUFT | ||||||
NOTE | Efficiency is tested by 530W, linear load at 13V, 26V, 52V input voltage. All parameters not specified above are measured at rated load, 25? of ambient temperature and set to factory setting. 3.lnput derating capacity referenced by curve 2. Output derating capacity referenced by curve 1. The tolerance of each voltage value by models is:112/212?±0.5V;124/224?±1V;148/248?±2V 6.THD is tested by 700W, linear load at 13,26,52V input voltage. |